Product Description
Turck IMX12-AI01-1I-1IU1R-H0/24VDC/CC Transmitter power supply isolator
The Turck IMX12-AI01-1I-1IU1R-H0/24VDC/CC is a transmitter power supply isolator. Signal type analog input, one channel, SIL 2 acc. to IEC 61508, relay output, protection class IP20, supply 24 VDC, ambient temperature from -25 °C, housing made of plastic. Ident no. 7580311, EAN 4047101311174.
Features
- Wire-break and short-circuit monitoring on input circuits
- Complete galvanic isolation
- HART transparent
- Removable spring-type terminals
- ATEX, IECEx
- For use in Zone 2
- SIL 2 BU
Technical data
Displays/controls (15)
| Error indication |
red |
| Power on display |
Green |
| Switching state |
Yellow |
| Messsignale aus dem explosionsgefährdeten |
Bereich in den sicheren Bereich. |
| Unterschreiten eines einstellbaren Grenzwerts. |
devices are suitable for operation in |
| transducer sowie aktive and passive betrieben werden. |
HART-Transmitter im Ex-Bereich |
| (optionally as Quelle or Senke) and 1…5 |
V (Quelle). Die Eingangssignale |
| Bereich in den sicheren Bereich an output |
[A1A] übertragen. Alternativ wird |
| 5 V (Quelle) an output [A2A] bereitgestellt. |
Darüber hinaus ist eine |
| input circuit wird to wire break and short circuit |
überwacht. |
| A1A or Voltage output A2A) sowie |
der Switching point (von 5…20 mA in 1- |
| Schaltverhalten des Relaisausgangs (A1D) eingestellten Schaltpunkts. |
at Überschreiten/Unterschreiten des |
| wire break and short circuit im input circuit |
ist each eine rote Status-LED |
| Stromwert < 3,5 mA bzw. Spannungswert |
< 0,875 V ausgegeben. |
| according to IEC 61508) and meets the requirements |
of the NE21. |
Ambient conditions (12)
| Ambient temperature |
-25...+70 °C |
| Storage temperature |
-40…+80 °C |
| Relative humidity |
95 % |
| Altitude |
max. 2000 m |
| Pollution degree |
2 |
| Surge category |
II (EN 61010-1) |
| Spannungsfestigkeit and Isolation |
EN 50178, EN 61010-1, EN 50155, GL VI-7-2 |
| Schock |
EN 61373 Klasse B, EN 50155, GL VI-7-2, EN 60068-2-6, EN 60068-2-27 |
| Temperatur |
EN 60068-2-1 Ad, EN 50155, GL VI-7-2, EN 60068-2-2 Bd, EN 60068-2-1 |
| Luftfeuchtigkeit |
EN 60068-2-38 |
| EMV |
EN 50155, NE21, EN 61326-1, EN 61326-3-1, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-4-11, EN 61000-4-29, EN 55011, EN 55016, EN 50121-3-2, EN 61000-6-2 |
| Protection class |
IP20 |
Outputs (10)
| Output switching voltage relay |
30 VDC/250 VAC |
| Digital output |
Relay output |
| Fall time (90…10 %) |
≤5 ms |
| Load resistance current output |
≤0,8 kΩ |
| Output circuits (digital) |
1 x Relais (NO contact) |
| Output current |
Source/sink 4…20 mA (sink: 15…28 V) |
| Output voltage |
1…5 V |
| Rise time (10…90 %) |
≤5 ms |
| Switching capacity per output |
≤500 VA/60 W |
| Switching current per output |
≤2 A |
Mechanical data (7)
| Dimensions |
120 mm x 12,5 mm x 128 mm |
| Housing material |
Plastic, Polycarbonate/ABS |
| Electrical connection |
Removable spring-type terminals, 2-pin |
| Terminal cross-section |
0.2…2.5 mm² (AWG: 24…14) |
| Design |
Modular housing |
| Suitable for row installation |
yes |
| Mounting instructions |
DIN rail (NS35) |
Power supply (6)
| Operating voltage UB |
10…30 VDC |
| Nominal voltage |
24 VDC |
| Power consumption |
≤ 4 W |
| Power dissipation, typical |
≤ 1,5 W |
| Nominal voltage |
24 VDC |
| Power supply |
24 VDC |
Tests/approvals (5)
| Important note |
For Ex-applications the values specified in the corresponding Ex certificates (ATEX, IECEx, UL, etc.) apply. |
| Important note |
If the device is used in applications to achieve functional safety according to IEC 61508, the safety manual must be used. Information in the data sheet are not valid for functional safety. |
| Ex approval acc. to conformity certificate |
IECEx TUN15.0031X |
| Device designation |
II (1) G, II (1) D [Ex ia Ga] IIC; [Ex ia Da] IIIC |
| Device designation |
II 3 (1) G Ex ec [ia Ga] IIC T4 Gc |
Galvanic isolation (4)
| Input 1 to output 1 |
375 V peak value acc. to EN 60079-11 |
| Input 1 to supply |
375 V peak value acc. to EN 60079-11 |
| Output 1 to supply |
50 V RMS acc. to EN 50178 and EN 61010-1 |
| Test voltage |
2.5 kV RMS |
Accuracy/deviation (3)
| Reference temperature |
23 °C |
| Measuring accuracy (including linearity, hysteresis and repeatability) |
≤ 0,05 % v. E. |
| Temperature drift |
≤0,002 % v.E. / K |
General data (2)
| Device type |
Isolating transducer |
| Signal type |
Analog input (HART transparent) |
Electrical data (2)
| Current output |
In mA |
| Voltage output |
In V |
Inputs (2)
| Input current |
4…20 mA |
| Supply voltage |
17 V/20 mA typ. |
Standards/directives (2)
| Flammability class acc. to UL 94 |
V-0 |
| Use in SIL safety circuits |
SIL 2 acc. to IEC 61508 acc. to IEC 61508 |
Safety specifications (1)
| Functional safety (SIL/PL) |
SIL 2 |
Inputs/Outputs (1)
Delivery time and availability
For urgent orders please ask us for the exact delivery time in advance; on request we check express shipping.
Your Benefits With Us
- Worldwide shipping of all Turck fieldbus and interface products
- Large stock levels for many products – current lead time available on request
- Terminal blocks, terminating resistors, gateways and connection cables available on request
- Fast shipping via UPS (parcel) or freight forwarder (pallets), express delivery available on request
- Extensive hands-on application know-how
- Personal advice on selecting the right component
- Resellers receive volume-based discounts on request
- Large companies, public authorities and government agencies can order on account (request via our contact form)